Air-Cooled

In Van Air AC series air-cooled after-coolers, hot compressed air is introduced to the core as ambient air is drawn across it, leaving the exiting air cooler. AC series after-coolers are normally sized for a 15°F (or less) approach to ambient air. For example, a compressor discharges 250°F air and the after-cooler is located in 80°F ambient conditions. With a 15°F approach, the air exiting the after-cooler will be 95°F and saturated, and the moisture created by cooling from 250°F to 95°F will condense.

 

 

 

 

 

 

 

Features and Benefits

  • Horizontal or vertical flow directions
  • Galvanized steel cabinet
  • Open vented motor
  • Pressure drop less than 3 psi at 80-125 psig